| Power Inlet Line Filter for Medical Equipment |
  
UL Recognized
CSA Certified
VDE Approved
15A versions are tested by Underwriters Laboratories to US and Canadian requirements and are
VDE approved at 10A, 250VAC
Catalog Data Sheet
Printer friendly version |
|
 |
H Series
- Minimal leakage current suitable for medical equipment
- Two element circuit provides basic EMI attenuation above 1 MHz
- Available with an internal ground circuit inductor
(C suffix versions) to isolate equipment chassis from
power line ground at radio frequencies
- Flanged mounting the same as the EC, ED and EF Series
- Capacitive output (see EAH, EBH and EJH Series for capacitive input)
Ordering Information

* IEC 60320-1 C14 inlet mates with C13 connector
Available Part Numbers
Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.
|
|
Specifications
| Maximum leakage current, each Line to Ground: |
| |
@ 120 VAC 60 Hz |
2 µA |
| |
@ 250 VAC 50 Hz |
5 µA |
| |
|
|
| Hipot rating (one minute): |
| |
Line to Ground |
2250 VDC |
| |
Line to Line |
1450 VDC |
| |
|
|
| Operating Frequency: |
50 / 60 Hz |
| |
|
|
| Rated voltage (max.): |
250 VAC |
| |
|
|
| Rated Current: |
3A to 15A |
| |
|
| Operating Ambient Temperature Range (at rated current Ir): |
| |
|
-10°C to +40°C |
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45
|
| |
|
Electrical Schematic

Accessories
GA400: NEMA 5-15P to IEC 60320-1 C13 line cord

|
| Case Styles |
H1 (Chassis Mount)

| Typical Dimensions: |
| |
Mounting holes (2): |
.188 [4.78] Dia. |
| |
Line/Load Terminals (4): |
.250 [6.35] with .07 [1.8] Dia. hole |
| |
Ground Terminal (1): |
.250 [6.35] with .07 x .16 [1.8 x 4.1] slot |
H3 (Chassis Mount)

| Typical Dimensions: |
| |
Mounting holes (2): |
.188 [4.78] Dia. |
| |
Wire Leads (5): |
4.0 [101.6] Min., 18AWG, UL1015 |
H4 & H4C

| Typical Dimensions: |
| |
Mounting holes (2): |
.132 [3.35] Dia. |
| |
Line Inlet (1): |
IEC 60320-1 C14 |
| |
Load Terminals (2): |
.250 [6.35] with .07 [1.8] Dia. hole |
| |
Ground Terminal (1): |
.250 [6.35] with .07 x .16 [1.8 x 4.1] slot |
H9

| Typical Dimensions: |
| |
Mounting holes (2): |
.132 [3.35] Dia. |
| |
Line Inlet (1): |
IEC 60320-1 C14 |
| |
Load Terminals (2): |
.250 [6.35] with .07 [1.8] Dia. hole |
| |
Ground Terminal (1): |
.250 [6.35] with .07 x .16 [1.8 x 4.1] slot |
|
|
H5

| Typical Dimensions: |
| |
Mounting holes (2): |
.132 [3.35] Dia. |
| |
Line Inlet (1): |
IEC 60320-1 C14 |
| |
Wire Leads: |
4.0 [101.6] Min., 18AWG, UL1015 |
H8

| Typical Dimensions: |
| |
Mounting holes (2): |
.132 [3.35] Dia. |
| |
Line Inlet (1): |
IEC 60320-1 C14 |
| |
Wire Leads: |
4.0 [101.6] Min., 18AWG, UL1015 |
Recommended Panel Cutouts

Note 1: H4, H4C and H8 allow for front or back mounting
Note 2: H5 and H9 allow for back mounting only
Case Dimensions
| Part No. |
A |
B |
C |
D |
E |
F |
| (max.) |
(max.) |
(max.) |
±.015 |
(max.) |
(ref..) |
| ± .38 |
| H1 |
2.25 |
1.82 |
0.66 |
2.125 |
2.53 |
|
| 57.2 |
46.1 |
16.7 |
53.98 |
64.2 |
|
|
| H3 |
.96 |
1.82 |
0.66 |
2.125 |
2.53 |
|
| 24.40 |
46.1 |
16.7 |
53.98 |
64.2 |
|
|
| 6EH4 |
2.20 |
1.19 |
0.81 |
1.575 |
1.98 |
|
| 55.9 |
30.2 |
20.6 |
40.01 |
50.3 |
|
|
| 10EH4, 10EH4C |
2.62 |
1.19 |
0.81 |
1.575 |
1.98 |
|
| 66.5 |
30.2 |
20.6 |
40.01 |
50.3 |
|
|
| 15EH4 |
2.62 |
1.19 |
0.81 |
1.575 |
1.98 |
|
| 66.5 |
30.2 |
20.6 |
40.01 |
50.3 |
|
|
| H5 |
1.55 |
1.19 |
0.85 |
1.575 |
1.98 |
.295 |
| 39.4 |
30.2 |
21.6 |
40.01 |
50.3 |
7.5 |
|
| H8 |
1.56 |
1.19 |
0.81 |
1.575 |
1.98 |
.295 |
| 39.7 |
30.2 |
20.6 |
40.01 |
50.3 |
7.5 |
|
| H9 |
1.55 |
1.19 |
0.85 |
1.575 |
1.98 |
|
| 39.4 |
30.2 |
21.6 |
40.01 |
50.3 |
|
|
|
Performance Data
| Typical Insertion Loss |
| Measured in closed 50 ohm system |
| |
3EH

|
6EH

|
10EH

|
15EH

|
 |
| Minimum Insertion Loss in dB: |
| Measured in closed 50 ohm system |
| |
|
|
| Common Mode / Asymmetrical (Line to Ground) |
|
Differential Mode / Symmetrical (Line to Line) |
|
|
|
| Current Rating |
Frequency - MHz |
| .15 |
.5 |
1 |
5 |
10 |
30 |
|
| 3A |
18 |
27 |
30 |
30 |
27 |
18 |
| 6A |
9 |
16 |
20 |
26 |
23 |
18 |
| 10A |
7 |
13 |
15 |
17 |
16 |
14 |
| 15A |
5 |
9 |
11 |
12 |
11 |
9 |
|
|
|
|
|
| USA Customer Service: |
1-800-468-2023 |
| Corcom Products Direct: |
1-847-680-7400 |
| Germany: |
49-89-6089-0 |
|
|
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. |