Skip to content
Home > Series > 3Phase > CFN

CFN Series

3-phase Delta Power Line Filter for High Voltage Applications


UL Recognized*

*400CFN12 only

Catalog Data Sheet
Printer friendly version

 

CFN Series

  • Universal high current filter
  • Suitable for industrial applications including; motor drives, inverters, converters, uninterruptible power supplies and mining equipment

Ordering Information

Available Part Numbers

Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.

300CFN12 500CFN12
400CFN12 600CFN12

 

 

Specifications

Maximum leakage current at 10% unsymetrical mains
Each Line to Ground (3 Phase WYE Center Tapped)*:
  @ 120 VAC 60 Hz 5.0 mA
  @ 250 VAC 50 Hz 9.6 mA
  * If 2 phases are interrupted, this leakage current may rise
to a significantly higher level
     
Hipot rating (one minute):
  Line to Ground 2210 VDC
  Line to Line 2158 VDC
     
Operating Frequency: 50 / 60 Hz
     
Rated voltage (max.):  
  Phase to Phase 480 VAC
  Phase to Ground 277 VAC
     
Rated Current: 300 to 600A
   
Operating Ambient Temperature Range (at rated current Ir):
-10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45

Electrical Schematic

 

Case Styles

Typical Dimensions:
  Copper Bar Terminals (6) 1.18 x 0.31 [29.97 x 7.84] with .413 [10.5] holes
  Screw Terminals (2): M12
Torque 22 lbf-in. [2.49 N-m] max.
  Inserts (4): M5 threaded, 1.1 lbf-in. [.12 N-m] max.

Case Dimensions

Part No. A B C D D1 E F G H
(max.) (max.) (max.) (ref.) (max.) ‡ .02 (max.) ‡ .02 (ref.)

300, 400, 500 &
600CFN12
24.8 11.81 6.30 22.20 20.31 10.83 9.84 8.66 5.0
630 300 160 564 516 275 250 220 127

 

Performance Data

Typical Insertion Loss
Measured in closed 50 ohm system
 

300, 400, 500 & 600CFN12

 

 

 

Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
     
Common Mode / Asymmetrical (Line to Ground)   Differential Mode / Symmetrical (Line to Line)

 
Current Rating Frequency - MHz
.01 .03 .07 .1 .15 .5 1 5 10 30

300 to 600A 10 19 26 40 55 82 76 51 37 20

 
Current Rating Frequency - MHz
.01 .03 .07 .1 .15 .5 1 5 10 30

300 to 600A 32 40 27 55 70 66 57 40 34 20

 

 

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
  Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.