AYC Series

3-Phase WYE RFI Power Line Filters for High Noise Applications


UL Recognized*

*All except 200AYC10B

Catalog Data Sheet
Printer friendly version

 

AYC Series

  • For 3-phase, four wire, WYE applications
  • Very high attenuation
  • Low leakage current
  • Ideal for EMC troubleshooting and refurbishing in the field
  • Touch safe terminals provide easy connections and prevent inadvertent contact for safety in the most demanding applications

Ordering Information

Available Part Numbers

Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.

16AYC10B 110AYC10B
25AYC10B 150AYC10B
36AYC10B 150AYC10B-95
63AYC10B 180AYC10B
80AYC10B 200AYC10B
 

Specifications

Maximum leakage current, each Line to Ground:
    @ 120 VAC 60 Hz: @ 250 VAC 50 Hz:
  16A 62 mA 106 mA
  25 & 36A 68 mA 118 mA
  63A 74 mA 128 mA
  80, 100 & 150A 74 mA 129 mA
  180 & 200A 111 mA 192 mA
       
Hipot rating (one minute):
  Line to Ground   1850 VDC
  Line to Line   1850 VDC
  Line to Neutral   1450 VDC
       
Operating Frequency:   50 / 60 Hz
       
Rated voltage (max.):    
  Phase to Phase   480 VAC
  Phase to Ground   277 VAC
       
Rated Current:   16A to 200A
     
Operating Ambient Temperature Range (at rated current Ir):
-10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45

Electrical Schematic

 

Case Styles

16, 25, 36 & 63AYC10B

80, 110 & 150 AYC10B / -95

180 & 200AYC10B

 

 

Case Dimensions

Part No. A B C D E
(max.) (max.) (max.) (max.) ± .078
± .2
16AYC10B 6.69 4.37 2.56 4.92 2.76
170.0 111.0 65.0 125.0 70.0

25AYC10B 9.96 5.08 2.52 5.71 4.53
246.0 129.0 64.0 145.0 115.0

36AYC10B 10.35 5.08 2.52 5.71 4.53
263.0 129.0 64.0 145.0 115.0

63AYC10B 10.89 5.08 2.52 5.71 4.53
279.0 129.0 64.0 145.0 115.0

80, 100 &
150AYC10B
12.09 5.55 5.55 6.10 4.53
307.0 141.0 141.0 155.0 115.0

150AYC10B-95 12.59 5.55 5.55 6.10 4.53
320.0 141.0 141.0 155.0 115.0

180 & 200AYC10B 15.71 5.55 5.55 6.10 3.25
399.0 141.0 141.0 155.0 82.5

 

Terminals

Part No. Terminal Size Torque max.
lbf-in [N-m]

16AYC10B Ground M5 26.58 [3.0]
Line / Load 4mm²
terminal block
7.08 [0.8]

25AYC10B Ground M5 26.58 [3.0]
Line / Load 6mm²
terminal block
15.93 [1.8]

36AYC10B Ground M5 26.58 [3.0]
Line / Load 10mm²
terminal block
15.93 [1.8]

63AYC10B Ground M6 53.1 [6.0]
Line / Load 16mm²
terminal block
20.35 [2.3]

80, 110 &
150AYC10B
Ground M10 177.0 [20.0]
Line / Load 50mm²
terminal block
70.80 [8.0]

150AYC10B-95,
180AYC10B &
200AYC10B
Ground M10 177.0 [20.0]
Line / Load 95mm²
terminal block
177.0 [20.0]

 

Performance Data

Typical Insertion Loss
Measured in closed 50 ohm system
 

16AYC10B

25AYC10B

36AYC10B

63AYC10B

80AYC10B

110AYC10B

150AYC10B

180 & 200AYC10B

Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
     
Common Mode / Asymmetrical (Line to Ground)   Differential Mode / Symmetrical (Line to Line)

 
Part No. Frequency - MHz
.01 .05 .1 .5 1 5 10 30

16AYC10B 23 66 82 88 82 79 55 21
25AYC10B 26 68 83 93 88 68 45 4
36AYC10B 18 61 78 96 91 71 49 7
63AYC10B 11 57 72 90 86 68 44 4
80AYC10B 10 57 75 84 77 75 62 45
110AYC10B 10 51 60 88 84 74 50 12
150AYC10B - 50 57 82 79 75 51 7
150AYC10B-95 1 51 55 85 82 84 51 11
180, 200AYC10B 3 53 55 97 89 81 56 20

 
Part No. Frequency - MHz
.01 .05 .1 .5 1 5 10 30

16AYC10B 21 32 54 90 86 73 72 47
25AYC10B 23 33 60 100 95 87 70 38
36AYC10B 25 37 51 94 87 69 58 17
63AYC10B 27 45 41 84 77 63 61 43
80AYC10B 37 42 67 87 80 66 60 50
110AYC10B 27 35 39 75 72 51 44 31
150AYC10B 28 37 42 74 67 52 45 30
150AYC10B-95 28 40 42 73 66 51 44 31
180, 200AYC10B 30 41 50 70 64 49 42 26

 

 

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0