Skip to content
Home > Series > 3Phase > A

A Series

High Performance 3-Phase RFI Power Line Filters for WYE Applications


UL Recognized
CSA Certified
VDE Approved

Catalog Data Sheet
Printer friendly version

 

A Series

  • For 3-phase, four wire, WYE Applications
  • Filters each of the three lines plus the neutral and ground line
  • Both common mode and differential mode suppression from 50kHz to 30MHz
  • Effective for both balanced and unbalanced loads
  • Ground choke included
  • Optional end bell kits available to shield input and output terminals
  • AYP single stage for lower noise environments
  • AYT dual stage provides highest performance

Ordering Information

Available Part Numbers

Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.

20AYP6C 20AYT6C
30AYP6C 30AYT6C
45AYP6C 45AYT6C
60AYP6C 60AYT6C

 

 

 

 

Specifications

Maximum leakage current, each Line to Ground:
  @ 120 VAC 60 Hz 1.4 mA
  @ 250 VAC 50 Hz 3.4 mA
     
Hipot rating (one minute):
  Line to Ground 1500 VAC
  Neutral to Ground 1500 VAC
  Line to Neutral 1450 VDC
     
Operating Frequency: 50 / 60 Hz
     
Rated voltage (max.):  
  Phase to Phase 440 VAC
  Phase to Neutral / Ground 250 VAC
     
Rated Current: 20A to 60A
   
Operating Ambient Temperature Range (at rated current Ir):
  -10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45

Electrical Schematics

AYP6C Models

AYT6C Models

 

Case Styles

Case Dimensions

Part No. A* B C D E
(max.) (max.) (max.) ± .030 ± .015
± .76 ± .38
20AYP6C
30AYP6C
8.82 5.57 2.56 4.616 1.50
224.0 141.5 65.0 117.2 38.1

45AYP6C
60AYP6C
9.43 6.92 4.82 5.950 3.75
239.5 175.8 122.4 151.1 95.3

20AYT6C
30AYT6C
13.82 5.57 2.56 4.616 1.50
351.0 141.5 65.0 117.2 38.1

45AYT6C
60AYT6C
13.83 6.92 4.82 5.950 3.75
351.3 175.8 122.4 151.1 95.3

* For end bell covering terminals and connections, add:
20A & 30A 5.57  
141.48
45A & 60A 6.45
163.83
 

Accessories

Mounting bracket kit with captive nuts:

AA400: 20A & 30A versions
AA405: 45A & 60A versions

Protective cover for use with mounting bracket (Available in Europe only):

AA406A: 20A & 30A versions
AA407A: 45A & 60A versions


End bell kit (bracket and cover) with captive nuts:

AA406: 20A & 30A versions
AA407: 45A & 60A versions

Additional captive nuts

AA401: 10 nuts

Performance Data

Typical Insertion Loss
Measured in closed 50 ohm system
 

20AYP6C

30AYP6C

45AYP6C

60AYP6C

20AYT6C

30AYT6C

45AYT6C

60AYT6C

Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
     
Common Mode / Asymmetrical (Line to Ground)   Differential Mode / Symmetrical (Line to Line)

 
Current Rating Frequency - MHz
.05 .1 .15 .5 1 5 10 30

AYP6C
20A 22 32 39 55 56 65 65 54
30A 15 24 30 55 55 61 63 50
45A 8 19 25 49 49 56 58 45
60A 5 16 22 50 50 54 54 47
AYT6C
20A 45 63 70 75 75 75 75 65
30A 29 53 61 75 75 75 75 60
45A 15 39 43 75 75 75 75 50
60A 12 37 46 75 75 75 70 45
 
Current Rating Frequency - MHz
.05 .1 .15 .5 1 5 10 30

AYP6C
20A 20 38 50 65 65 65 60 52
30A 18 28 43 65 65 65 59 48
45A 8 20 27 60 65 65 56 43
60A 20 24 27 60 65 65 56 50
AYT6C
20A 27 56 65 70 70 70 70 70
30A 17 46 55 75 75 75 75 70
45A 14 41 50 75 75 75 75 65
60A 26 50 58 75 75 75 75 60

 

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
  Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.